ClimaStrat Project App v1.4
Engineering Workspace · Generic Geocode + Multi-Performance

← Projekte   CS-2026-NI-VEL-0001

ASML Niederlande

Standort
Veldhoven, Niederlande
Quick Assessment
30000.0 m² · 12000.0 Paneele · 150000 m³/h CALCULATED

Climate / EPW

Jeddah.epw
Jeddah-Abdulaziz.Intl.AP, SAU · 8760 h
SHA-256 bb1afd72ea9a42f2…

ARE_AZ_Abu.Dhabi-Bateen.Exec.AP.412160_TMYx.2011-2025.epw
Abu.Dhabi-Bateen.Exec.AP, ARE · 8760 h
SHA-256 1631528ee2411ae6…

HUN_NGP_Szolnok.AB.128600_TMYx.2011-2025.epw
Szolnok.AB, HUN · 8760 h
SHA-256 1664a3cfe2204bf5…

ARE_DU_Dubai.Minhad.Ab.412164_TMYx.2011-2025.epw
Dubai.Minhad.Ab, ARE · 8760 h
SHA-256 95fe708d2331b0e9…

TWN_NOR_Hsinchu.AP.467560_TMYx.2011-2025.epw
Hsinchu.AP, TWN · 8760 h
SHA-256 a1dd22c483401272…

ESP_IB_Palma.de.Mallorca.AP-Son.San.Juan.AFB.083060_TMYx.2011-2025.epw
Palma.de.Mallorca.AP-Son.San.Juan.AFB, ESP · 8760 h
SHA-256 7533d562dfae5564…

NLD_NB_Eindhoven.AP.063700_TMYx.2011-2025.epw
Eindhoven.AP, NLD · 8760 h
SHA-256 5a4dd2b22593d6bb…

Neues Szenario

Operating = ASSUMED

Scenarios

IDEPWAFDTinnxStatus
BASE-20260928103104NLD_NB_Eindhoven.AP.063700_TMYx.2011-2025.epw5.016.016READY · AUTO_COOLING

Simulation Results

RunScenarioClimateWater m³/aCond hCooling hTotal MWhth/aEvidenceView / Actions
RUN-20260928103214BASE-20260928103104NLD_NB_Eindhoven.AP.063700_TMYx.2011-2025.epw40.9812962225398.361MODELLED

CS-ENGINE-0.4.7.1 · forced-flow baseline · mixed convection NOT APPLIED · physical yield TO BE VALIDATED.

Energy & PV Baseline

Energy result: RUN-20260928103214 · Scenario: BASE-20260928103104

MetricValueEvidence
Cooling electricity99.59 MWh/aCALCULATED · COP ASSUMED
Fan electricity0.24 MWh/aMODELLED / CALCULATED
Fan Δp1.540 PaMODELLED_GAP_PLUS_LOCAL
Fan electric power106.93 WMODELLED
Gap air velocity0.556 m/sMODELLED
Fan Reynolds number3544MODELLED
Flow regimeTRANSITIONCALCULATED CLASSIFICATION
f laminar (64/Re)0.01806CALCULATED COMPARATOR
f Swamee-Jain0.04231MODELLED COMPARATOR
f Churchill0.04228MODELLED · TRANSITION CAPABLE
Δp gap – Swamee-Jain1.541 PaMODELLED COMPARATOR
Δp gap – Churchill1.540 PaMODELLED COMPARATOR
Local loss ΣK0.00ASSUMED
Δp local0.000 PaCALCULATED FROM ASSUMED K
Δp system1.540 PaMODELLED
Fan efficiency η0.60ASSUMED
Fan modelDARCY_WEISBACH_WIDE_GAP_CHURCHILLMODELLED
Pump electricity0.15 MWh/aMODELLED / CALCULATED
Pump total flow1287.5 L/minCALCULATED
Pump peak flow7778.8 L/minMODELLED
Coolant design ΔT2.00 KASSUMED
Hydraulic zones120CALCULATED FROM PANELS / ZONE
Panels / hydraulic zone100ASSUMED / TO BE ENGINEERED
Zone pipe80 mm · 40.0 mASSUMED
Zone pipe velocity0.036 m/sMODELLED
Zone pipe Δp23.2 PaMODELLED
Main hydraulic loops1ASSUMED ARCHITECTURE
Main pipe300 mm · 100.0 mASSUMED
Main pipe velocity0.304 m/sMODELLED
Main pipe Δp861.9 PaMODELLED
Channel flow0.005 L/minCALCULATED
Coolant velocity0.001 m/sMODELLED
Coolant Reynolds8MODELLED
Channel Δp5.5 PaMODELLED · RECTANGULAR LAMINAR
Pump system Δp890.5 PaMODELLED
Pump electric power66.58 WMODELLED
Pump peak electric power3838.66 WMODELLED
Optimizer criterionCONSTRAINED_ENERGY_INFRASTRUCTURE_PARETOMODELLED DESIGN SEARCH
Optimizer balanced loops1MODELLED
Optimizer balanced main Ø400 mmMODELLED
Optimizer balanced pump energy0.05 MWh/aMODELLED COMPARATIVE
Optimizer balanced peak velocity1.03 m/sMODELLED
Optimizer feasible variants16 / 36CALCULATED
Energy-min variant2 loops · Ø 500 mm · 0.01 MWh/aMODELLED COMPARATIVE
Infrastructure-min variant1 loops · Ø 250 mm · proxy 4.9 m³MODELLED PROXY
Pareto variants13CALCULATED
Total CS electricity99.98 MWh/aCALCULATED
EPW GHI1123.35 kWh/m²aSOURCE_DATA
PV area21000.00 m²CALCULATED FROM SURFACES
Installed PV4200.00 kWpCALCULATED
PV generation3966.89 MWh/aMODELLED
PV reference planeORIENTED_POA_ISOTROPIC_SKYMODELLED
PV transpositionISOTROPIC_SKYMODELLED
Annual energy balance3866.92 MWh/aCALCULATED
Hourly CS load99.98 MWh/aCALCULATED FROM HOURLY MODEL
PV direct use85.82 MWh/aCALCULATED · NO STORAGE
PV surplus3881.07 MWh/aCALCULATED · NO STORAGE
Grid import14.15 MWh/aCALCULATED · NO STORAGE
PV self-consumption0.022CALCULATED · DIRECT PV / PV
CS self-sufficiency0.858CALCULATED · DIRECT PV / CS LOAD
Peak CS load274.36 kWMODELLED / CALCULATED
Peak PV3110.19 kWMODELLED
Peak grid import142.85 kWCALCULATED

Hourly Energy Diagnostics

DiagnosticValueEvidence
CS active hours2225CALCULATED
Hours with PV surplus4536CALCULATED
Hours with grid import488CALCULATED
Active CS hours fully supplied by PV1737CALCULATED · NO STORAGE
Maximum PV surplus3072.94 kWCALCULATED
Maximum deficit / grid import142.85 kWCALCULATED

Monthly Energy Matching

MonthCS MWhPV MWhDirect MWhSurplus MWhGrid MWhCS self-suff.PV self-cons.
Jan0.0080.710.0080.710.000.0%0.0%
Feb0.00147.800.00147.800.000.0%0.0%
Mar0.00327.750.00327.740.00100.0%0.0%
Apr1.50454.291.48452.810.0199.0%0.3%
May7.02598.106.90591.210.1298.2%1.2%
Jun22.29599.1219.68579.442.6188.3%3.3%
Jul26.88550.8122.70528.114.1784.5%4.1%
Aug30.34517.7325.55492.174.7984.2%4.9%
Sep11.15343.208.78334.412.3778.7%2.6%
Oct0.79195.480.72194.750.0791.6%0.4%
Nov0.0093.740.0093.740.000.0%0.0%
Dec0.0058.170.0058.170.000.0%0.0%

Energy Matching by EPW Hour

EPW hourCS MWh/a-binPV MWh/a-binDirectSurplusGrid
011.380.000.000.001.38
021.180.000.000.001.18
030.920.000.000.000.92
040.890.000.000.000.89
050.813.670.253.420.56
060.9926.160.8825.280.11
071.5076.571.5075.080.00
082.42156.302.42153.880.00
093.73260.173.73256.450.00
104.92370.654.92365.730.00
116.10459.276.10453.170.00
127.05506.927.05499.870.00
137.90509.607.90501.700.00
148.36476.638.36468.270.00
158.74407.698.74398.950.00
168.77311.728.77302.950.00
178.30210.568.30202.250.00
187.30122.277.30114.970.01
195.8454.335.7048.630.14
204.4613.283.309.981.16
212.931.100.600.502.32
222.180.000.000.002.18
231.750.000.000.001.75
241.560.000.000.001.56

EPW hours are end-of-hour labels (1–24). Diagnostics aggregate the same hourly arrays used by v0.9.0; no storage or load shifting is applied.

v1.0 Energy Architecture

GRID-COUPLED PV WITHOUT STORAGE. PV is used directly when coincident with CS demand. Surplus is treated as grid export potential; deficits are grid import. Battery, chilled-water, PCM and ice storage are not part of the v1.0 product baseline. The storage investigation is preserved as a research branch.

v1.3 Advanced Grid Economics

MetricValueEvidence
Grid import14.15 MWh/aCALCULATED FROM HOURLY MATCHING
Grid export3881.07 MWh/aCALCULATED FROM HOURLY MATCHING
Curtailed export0.00 MWh/aCALCULATED
Import cost€ 1415.25/aCALCULATED · TARIFF PROJECT INPUT
Export revenue€ 58216.05/aCALCULATED · TARIFF PROJECT INPUT
Fixed grid cost€ 0.00/aPROJECT INPUT / ASSUMED
Peak grid import142.85 kWCALCULATED FROM 8760 HOURS
Demand charge€ 0.00/aCALCULATED · PROJECT INPUT
Weighted import price€ 100.00/MWhCALCULATED
Weighted export price€ 15.00/MWhCALCULATED
Net grid energy cost€ -56800.80/aCALCULATED
Break-even export price€ 0.36/MWhCALCULATED DIAGNOSTIC

v1.3 uses the actual 8760 hourly import/surplus arrays. Off-peak/peak tariffs, demand charge and export limit are PROJECT INPUT / ASSUMED. Economic post-processing only: no storage, no load shifting and no change to the physical baseline. Taxes and detailed grid fees are not yet modelled.

v1.4 Project Economics / Energy Cash Flow

MetricValueEvidence / boundary
Direct PV use85.82 MWh/aCALCULATED FROM 8760 HOURS
Direct PV avoided-purchase value€ 8582.38/aCALCULATED · COINCIDENT IMPORT TARIFF
Export revenue€ 58216.05/aFROM v1.3 GRID ECONOMICS
Gross energy value€ 66798.43/aCALCULATED
Annual project OPEX€ 0.00/aPROJECT INPUT / ASSUMED
Year-1 net project cash flow€ 66798.43CALCULATED · ENERGY-ONLY
Project CAPEX€ 0.00PROJECT INPUT / ASSUMED
NPV€ 655836.81CALCULATED · ENERGY-ONLY
Simple payback- yearsCALCULATED DIAGNOSTIC
Discounted payback- yearsCALCULATED DIAGNOSTIC

Energy-only project cash flow. Direct PV is valued at the coincident import tariff; export at v1.3 tariff. Demand/fixed grid charges are reported but not claimed as avoided investment benefits because a no-PV counterfactual peak/grid contract is not yet modelled. Water value, cooling-service value, taxes, financing and full ClimaStrat CAPEX allocation are excluded.

PV Surface Diagnostics

SurfaceAreaTiltAzimuthAnnual POAInstalledGenerationSpecific yield kWh/kWp·aShare
ROOF21000.00 m²0.0°180.0°1111.17 kWh/m²a4200.00 kWp3966.89 MWh/a944.5100.0%
SOUTH_FACADE0.00 m²90.0°180.0°905.86 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%
EAST_FACADE0.00 m²90.0°90.0°761.69 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%
WEST_FACADE0.00 m²90.0°270.0°616.29 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%

Azimuth: N=0°, E=90°, S=180°, W=270°. EPW GHI/DNI/DHI = SOURCE_DATA; POA and generation = MODELLED; module efficiency, PR and albedo = ASSUMED.