ClimaStrat Project App v1.4
Engineering Workspace · Generic Geocode + Multi-Performance

← Projekte   CS-2026-NI-VEL-0002

ASML Niederlande groß

Standort
Veldhoven, Niederlande
Quick Assessment
200000.0 m² · 80000.0 Paneele · 1000000 m³/h CALCULATED

Climate / EPW

Jeddah.epw
Jeddah-Abdulaziz.Intl.AP, SAU · 8760 h
SHA-256 bb1afd72ea9a42f2…

ARE_AZ_Abu.Dhabi-Bateen.Exec.AP.412160_TMYx.2011-2025.epw
Abu.Dhabi-Bateen.Exec.AP, ARE · 8760 h
SHA-256 1631528ee2411ae6…

HUN_NGP_Szolnok.AB.128600_TMYx.2011-2025.epw
Szolnok.AB, HUN · 8760 h
SHA-256 1664a3cfe2204bf5…

ARE_DU_Dubai.Minhad.Ab.412164_TMYx.2011-2025.epw
Dubai.Minhad.Ab, ARE · 8760 h
SHA-256 95fe708d2331b0e9…

TWN_NOR_Hsinchu.AP.467560_TMYx.2011-2025.epw
Hsinchu.AP, TWN · 8760 h
SHA-256 a1dd22c483401272…

ESP_IB_Palma.de.Mallorca.AP-Son.San.Juan.AFB.083060_TMYx.2011-2025.epw
Palma.de.Mallorca.AP-Son.San.Juan.AFB, ESP · 8760 h
SHA-256 7533d562dfae5564…

NLD_NB_Eindhoven.AP.063700_TMYx.2011-2025.epw
Eindhoven.AP, NLD · 8760 h
SHA-256 5a4dd2b22593d6bb…

Neues Szenario

Operating = ASSUMED

Scenarios

IDEPWAFDTinnxStatus
BASE-20260928103710NLD_NB_Eindhoven.AP.063700_TMYx.2011-2025.epw5.016.016READY · AUTO_COOLING

Simulation Results

RunScenarioClimateWater m³/aCond hCooling hTotal MWhth/aEvidenceView / Actions
RUN-20260928103827BASE-20260928103710NLD_NB_Eindhoven.AP.063700_TMYx.2011-2025.epw273.20829622252655.740MODELLED

CS-ENGINE-0.4.7.1 · forced-flow baseline · mixed convection NOT APPLIED · physical yield TO BE VALIDATED.

Energy & PV Baseline

Energy result: RUN-20260928103827 · Scenario: BASE-20260928103710

MetricValueEvidence
Cooling electricity663.93 MWh/aCALCULATED · COP ASSUMED
Fan electricity1.59 MWh/aMODELLED / CALCULATED
Fan Δp1.540 PaMODELLED_GAP_PLUS_LOCAL
Fan electric power712.83 WMODELLED
Gap air velocity0.556 m/sMODELLED
Fan Reynolds number3544MODELLED
Flow regimeTRANSITIONCALCULATED CLASSIFICATION
f laminar (64/Re)0.01806CALCULATED COMPARATOR
f Swamee-Jain0.04231MODELLED COMPARATOR
f Churchill0.04228MODELLED · TRANSITION CAPABLE
Δp gap – Swamee-Jain1.541 PaMODELLED COMPARATOR
Δp gap – Churchill1.540 PaMODELLED COMPARATOR
Local loss ΣK0.00ASSUMED
Δp local0.000 PaCALCULATED FROM ASSUMED K
Δp system1.540 PaMODELLED
Fan efficiency η0.60ASSUMED
Fan modelDARCY_WEISBACH_WIDE_GAP_CHURCHILLMODELLED
Pump electricity37.10 MWh/aMODELLED / CALCULATED
Pump total flow8583.6 L/minCALCULATED
Pump peak flow51858.4 L/minMODELLED
Coolant design ΔT2.00 KASSUMED
Hydraulic zones800CALCULATED FROM PANELS / ZONE
Panels / hydraulic zone100ASSUMED / TO BE ENGINEERED
Zone pipe80 mm · 40.0 mASSUMED
Zone pipe velocity0.036 m/sMODELLED
Zone pipe Δp23.2 PaMODELLED
Main hydraulic loops1ASSUMED ARCHITECTURE
Main pipe300 mm · 100.0 mASSUMED
Main pipe velocity2.024 m/sMODELLED
Main pipe Δp33131.5 PaMODELLED
Channel flow0.005 L/minCALCULATED
Coolant velocity0.001 m/sMODELLED
Coolant Reynolds8MODELLED
Channel Δp5.5 PaMODELLED · RECTANGULAR LAMINAR
Pump system Δp33160.1 PaMODELLED
Pump electric power16673.35 WMODELLED
Pump peak electric power993686.48 WMODELLED
Optimizer criterionCONSTRAINED_ENERGY_INFRASTRUCTURE_PARETOMODELLED DESIGN SEARCH
Optimizer balanced loops4MODELLED
Optimizer balanced main Ø500 mmMODELLED
Optimizer balanced pump energy0.31 MWh/aMODELLED COMPARATIVE
Optimizer balanced peak velocity1.10 m/sMODELLED
Optimizer feasible variants18 / 36CALCULATED
Energy-min variant10 loops · Ø 500 mm · 0.08 MWh/aMODELLED COMPARATIVE
Infrastructure-min variant2 loops · Ø 450 mm · proxy 31.8 m³MODELLED PROXY
Pareto variants15CALCULATED
Total CS electricity702.62 MWh/aCALCULATED
EPW GHI1123.35 kWh/m²aSOURCE_DATA
PV area140000.00 m²CALCULATED FROM SURFACES
Installed PV28000.00 kWpCALCULATED
PV generation26445.96 MWh/aMODELLED
PV reference planeORIENTED_POA_ISOTROPIC_SKYMODELLED
PV transpositionISOTROPIC_SKYMODELLED
Annual energy balance25743.34 MWh/aCALCULATED
Hourly CS load702.62 MWh/aCALCULATED FROM HOURLY MODEL
PV direct use604.66 MWh/aCALCULATED · NO STORAGE
PV surplus25841.30 MWh/aCALCULATED · NO STORAGE
Grid import97.96 MWh/aCALCULATED · NO STORAGE
PV self-consumption0.023CALCULATED · DIRECT PV / PV
CS self-sufficiency0.861CALCULATED · DIRECT PV / CS LOAD
Peak CS load2797.19 kWMODELLED / CALCULATED
Peak PV20734.62 kWMODELLED
Peak grid import1169.66 kWCALCULATED

Hourly Energy Diagnostics

DiagnosticValueEvidence
CS active hours2225CALCULATED
Hours with PV surplus4535CALCULATED
Hours with grid import489CALCULATED
Active CS hours fully supplied by PV1736CALCULATED · NO STORAGE
Maximum PV surplus20486.08 kWCALCULATED
Maximum deficit / grid import1169.66 kWCALCULATED

Monthly Energy Matching

MonthCS MWhPV MWhDirect MWhSurplus MWhGrid MWhCS self-suff.PV self-cons.
Jan0.00538.080.00538.080.000.0%0.0%
Feb0.00985.330.00985.330.000.0%0.0%
Mar0.032184.970.032184.940.00100.0%0.0%
Apr10.063028.619.973018.650.1099.0%0.3%
May47.743987.3546.913940.440.8498.2%1.2%
Jun156.183994.14138.183855.9618.0088.5%3.5%
Jul189.473672.09160.453511.6429.0284.7%4.4%
Aug217.223451.52183.733267.7933.5084.6%5.3%
Sep76.612287.9760.552227.4216.0679.0%2.6%
Oct5.291303.174.851298.320.4591.6%0.4%
Nov0.00624.950.00624.950.000.0%0.0%
Dec0.00387.770.00387.770.000.0%0.0%

Energy Matching by EPW Hour

EPW hourCS MWh/a-binPV MWh/a-binDirectSurplusGrid
019.460.000.000.009.46
028.210.000.000.008.21
036.270.000.000.006.27
046.060.000.000.006.06
055.5424.471.7122.773.84
066.80174.406.04168.370.76
0710.31510.4910.31500.180.00
0816.741042.0016.741025.260.00
0925.851734.4925.851708.640.00
1034.272471.0234.272436.750.00
1142.703061.8342.703019.130.00
1249.513379.4749.513329.960.00
1355.643397.3455.643341.700.00
1459.203177.5259.203118.320.00
1561.972717.9261.972655.960.00
1663.022078.1263.022015.100.00
1759.341403.7259.341344.380.00
1851.81815.1251.77763.350.04
1940.97362.1839.96322.221.01
2031.1288.5322.6265.918.50
2120.097.334.013.3216.08
2215.010.000.000.0015.01
2311.990.000.000.0011.99
2410.730.000.000.0010.73

EPW hours are end-of-hour labels (1–24). Diagnostics aggregate the same hourly arrays used by v0.9.0; no storage or load shifting is applied.

v1.0 Energy Architecture

GRID-COUPLED PV WITHOUT STORAGE. PV is used directly when coincident with CS demand. Surplus is treated as grid export potential; deficits are grid import. Battery, chilled-water, PCM and ice storage are not part of the v1.0 product baseline. The storage investigation is preserved as a research branch.

v1.3 Advanced Grid Economics

MetricValueEvidence
Grid import97.96 MWh/aCALCULATED FROM HOURLY MATCHING
Grid export25841.30 MWh/aCALCULATED FROM HOURLY MATCHING
Curtailed export0.00 MWh/aCALCULATED
Import cost€ 9795.81/aCALCULATED · TARIFF PROJECT INPUT
Export revenue€ 387619.46/aCALCULATED · TARIFF PROJECT INPUT
Fixed grid cost€ 0.00/aPROJECT INPUT / ASSUMED
Peak grid import1169.66 kWCALCULATED FROM 8760 HOURS
Demand charge€ 0.00/aCALCULATED · PROJECT INPUT
Weighted import price€ 100.00/MWhCALCULATED
Weighted export price€ 15.00/MWhCALCULATED
Net grid energy cost€ -377823.65/aCALCULATED
Break-even export price€ 0.38/MWhCALCULATED DIAGNOSTIC

v1.3 uses the actual 8760 hourly import/surplus arrays. Off-peak/peak tariffs, demand charge and export limit are PROJECT INPUT / ASSUMED. Economic post-processing only: no storage, no load shifting and no change to the physical baseline. Taxes and detailed grid fees are not yet modelled.

v1.4 Project Economics / Energy Cash Flow

MetricValueEvidence / boundary
Direct PV use604.66 MWh/aCALCULATED FROM 8760 HOURS
Direct PV avoided-purchase value€ 60466.11/aCALCULATED · COINCIDENT IMPORT TARIFF
Export revenue€ 387619.46/aFROM v1.3 GRID ECONOMICS
Gross energy value€ 448085.57/aCALCULATED
Annual project OPEX€ 0.00/aPROJECT INPUT / ASSUMED
Year-1 net project cash flow€ 448085.57CALCULATED · ENERGY-ONLY
Project CAPEX€ 0.00PROJECT INPUT / ASSUMED
NPV€ 4399370.17CALCULATED · ENERGY-ONLY
Simple payback- yearsCALCULATED DIAGNOSTIC
Discounted payback- yearsCALCULATED DIAGNOSTIC

Energy-only project cash flow. Direct PV is valued at the coincident import tariff; export at v1.3 tariff. Demand/fixed grid charges are reported but not claimed as avoided investment benefits because a no-PV counterfactual peak/grid contract is not yet modelled. Water value, cooling-service value, taxes, financing and full ClimaStrat CAPEX allocation are excluded.

PV Surface Diagnostics

SurfaceAreaTiltAzimuthAnnual POAInstalledGenerationSpecific yield kWh/kWp·aShare
ROOF140000.00 m²0.0°180.0°1111.17 kWh/m²a28000.00 kWp26445.96 MWh/a944.5100.0%
SOUTH_FACADE0.00 m²90.0°180.0°905.86 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%
EAST_FACADE0.00 m²90.0°90.0°761.69 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%
WEST_FACADE0.00 m²90.0°270.0°616.29 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%

Azimuth: N=0°, E=90°, S=180°, W=270°. EPW GHI/DNI/DHI = SOURCE_DATA; POA and generation = MODELLED; module efficiency, PR and albedo = ASSUMED.