ClimaStrat Project App v1.4
Engineering Workspace · Generic Geocode + Multi-Performance

← Projekte   CS-2026-TA-HSI-0001

TSMC Tajwan

Standort
Hsinchu, Taiwan
Quick Assessment
200000.0 m² · 80000.0 Paneele · 1000000 m³/h CALCULATED

Climate / EPW

Jeddah.epw
Jeddah-Abdulaziz.Intl.AP, SAU · 8760 h
SHA-256 bb1afd72ea9a42f2…

ARE_AZ_Abu.Dhabi-Bateen.Exec.AP.412160_TMYx.2011-2025.epw
Abu.Dhabi-Bateen.Exec.AP, ARE · 8760 h
SHA-256 1631528ee2411ae6…

HUN_NGP_Szolnok.AB.128600_TMYx.2011-2025.epw
Szolnok.AB, HUN · 8760 h
SHA-256 1664a3cfe2204bf5…

ARE_DU_Dubai.Minhad.Ab.412164_TMYx.2011-2025.epw
Dubai.Minhad.Ab, ARE · 8760 h
SHA-256 95fe708d2331b0e9…

TWN_NOR_Hsinchu.AP.467560_TMYx.2011-2025.epw
Hsinchu.AP, TWN · 8760 h
SHA-256 a1dd22c483401272…

ESP_IB_Palma.de.Mallorca.AP-Son.San.Juan.AFB.083060_TMYx.2011-2025.epw
Palma.de.Mallorca.AP-Son.San.Juan.AFB, ESP · 8760 h
SHA-256 7533d562dfae5564…

NLD_NB_Eindhoven.AP.063700_TMYx.2011-2025.epw
Eindhoven.AP, NLD · 8760 h
SHA-256 5a4dd2b22593d6bb…

Neues Szenario

Operating = ASSUMED

Scenarios

IDEPWAFDTinnxStatus
BASE-20260928091527TWN_NOR_Hsinchu.AP.467560_TMYx.2011-2025.epw5.016.016READY · AUTO_COOLING

Simulation Results

RunScenarioClimateWater m³/aCond hCooling hTotal MWhth/aEvidenceView / Actions
RUN-20260928091643BASE-20260928091527TWN_NOR_Hsinchu.AP.467560_TMYx.2011-2025.epw27836.3206028776935243.495MODELLED

CS-ENGINE-0.4.7.1 · forced-flow baseline · mixed convection NOT APPLIED · physical yield TO BE VALIDATED.

Energy & PV Baseline

Energy result: RUN-20260928091643 · Scenario: BASE-20260928091527

MetricValueEvidence
Cooling electricity8810.87 MWh/aCALCULATED · COP ASSUMED
Fan electricity5.54 MWh/aMODELLED / CALCULATED
Fan Δp1.540 PaMODELLED_GAP_PLUS_LOCAL
Fan electric power712.83 WMODELLED
Gap air velocity0.556 m/sMODELLED
Fan Reynolds number3544MODELLED
Flow regimeTRANSITIONCALCULATED CLASSIFICATION
f laminar (64/Re)0.01806CALCULATED COMPARATOR
f Swamee-Jain0.04231MODELLED COMPARATOR
f Churchill0.04228MODELLED · TRANSITION CAPABLE
Δp gap – Swamee-Jain1.541 PaMODELLED COMPARATOR
Δp gap – Churchill1.540 PaMODELLED COMPARATOR
Local loss ΣK0.00ASSUMED
Δp local0.000 PaCALCULATED FROM ASSUMED K
Δp system1.540 PaMODELLED
Fan efficiency η0.60ASSUMED
Fan modelDARCY_WEISBACH_WIDE_GAP_CHURCHILLMODELLED
Pump electricity4494.61 MWh/aMODELLED / CALCULATED
Pump total flow32623.3 L/minCALCULATED
Pump peak flow77439.6 L/minMODELLED
Coolant design ΔT2.00 KASSUMED
Hydraulic zones800CALCULATED FROM PANELS / ZONE
Panels / hydraulic zone100ASSUMED / TO BE ENGINEERED
Zone pipe80 mm · 40.0 mASSUMED
Zone pipe velocity0.135 m/sMODELLED
Zone pipe Δp232.5 PaMODELLED
Main hydraulic loops1ASSUMED ARCHITECTURE
Main pipe300 mm · 100.0 mASSUMED
Main pipe velocity7.692 m/sMODELLED
Main pipe Δp395858.6 PaMODELLED
Channel flow0.020 L/minCALCULATED
Coolant velocity0.006 m/sMODELLED
Coolant Reynolds29MODELLED
Channel Δp20.9 PaMODELLED · RECTANGULAR LAMINAR
Pump system Δp396112.0 PaMODELLED
Pump electric power578531.13 WMODELLED
Pump peak electric power3252401.54 WMODELLED
Optimizer criterionCONSTRAINED_ENERGY_INFRASTRUCTURE_PARETOMODELLED DESIGN SEARCH
Optimizer balanced loops4MODELLED
Optimizer balanced main Ø500 mmMODELLED
Optimizer balanced pump energy36.62 MWh/aMODELLED COMPARATIVE
Optimizer balanced peak velocity1.64 m/sMODELLED
Optimizer feasible variants14 / 36CALCULATED
Energy-min variant10 loops · Ø 500 mm · 8.52 MWh/aMODELLED COMPARATIVE
Infrastructure-min variant10 loops · Ø 250 mm · proxy 49.1 m³MODELLED PROXY
Pareto variants13CALCULATED
Total CS electricity13311.02 MWh/aCALCULATED
EPW GHI1592.05 kWh/m²aSOURCE_DATA
PV area140000.00 m²CALCULATED FROM SURFACES
Installed PV28000.00 kWpCALCULATED
PV generation37540.24 MWh/aMODELLED
PV reference planeORIENTED_POA_ISOTROPIC_SKYMODELLED
PV transpositionISOTROPIC_SKYMODELLED
Annual energy balance24229.22 MWh/aCALCULATED
Hourly CS load13311.02 MWh/aCALCULATED FROM HOURLY MODEL
PV direct use6886.64 MWh/aCALCULATED · NO STORAGE
PV surplus30653.60 MWh/aCALCULATED · NO STORAGE
Grid import6424.38 MWh/aCALCULATED · NO STORAGE
PV self-consumption0.183CALCULATED · DIRECT PV / PV
CS self-sufficiency0.517CALCULATED · DIRECT PV / CS LOAD
Peak CS load5945.20 kWMODELLED / CALCULATED
Peak PV22804.34 kWMODELLED
Peak grid import4724.98 kWCALCULATED

Hourly Energy Diagnostics

DiagnosticValueEvidence
CS active hours7769CALCULATED
Hours with PV surplus3956CALCULATED
Hours with grid import4162CALCULATED
Active CS hours fully supplied by PV3607CALCULATED · NO STORAGE
Maximum PV surplus21303.66 kWCALCULATED
Maximum deficit / grid import4724.98 kWCALCULATED

Monthly Energy Matching

MonthCS MWhPV MWhDirect MWhSurplus MWhGrid MWhCS self-suff.PV self-cons.
Jan37.702133.2928.752104.548.9576.2%1.3%
Feb42.902257.4732.102225.3710.8074.8%1.4%
Mar214.953242.12131.513110.6183.4461.2%4.1%
Apr566.783621.39311.873309.52254.9155.0%8.6%
May1355.013507.61721.322786.28633.6953.2%20.6%
Jun2137.243776.111138.602637.50998.6453.3%30.2%
Jul2703.744377.151409.112968.041294.6352.1%32.2%
Aug2574.344027.391299.912727.481274.4350.5%32.3%
Sep1741.473671.97866.152805.81875.3249.7%23.6%
Oct1182.632960.55568.042392.50614.5848.0%19.2%
Nov599.262208.84292.101916.74307.1648.7%13.2%
Dec155.001756.3787.181669.1967.8256.2%5.0%

Energy Matching by EPW Hour

EPW hourCS MWh/a-binPV MWh/a-binDirectSurplusGrid
01514.230.000.000.00514.23
02498.950.000.000.00498.95
03486.710.000.000.00486.71
04476.820.000.000.00476.82
05461.370.000.000.00461.37
06452.980.000.000.00452.98
07473.99275.00242.4232.57231.57
08504.561246.52486.69759.8317.87
09524.792554.02520.462033.564.32
10555.163800.24554.173246.081.00
11601.684746.80601.284145.520.40
12622.895249.40622.894626.510.00
13645.475262.55645.474617.080.00
14661.264819.81661.164158.660.11
15662.104003.27661.523341.750.58
16653.252945.59649.552296.053.70
17617.981772.18608.401163.789.58
18601.86705.11483.32221.79118.54
19571.28144.82134.4010.42436.88
20560.3914.9214.920.00545.47
21553.660.000.000.00553.66
22547.070.000.000.00547.07
23537.060.000.000.00537.06
24525.500.000.000.00525.50

EPW hours are end-of-hour labels (1–24). Diagnostics aggregate the same hourly arrays used by v0.9.0; no storage or load shifting is applied.

v1.0 Energy Architecture

GRID-COUPLED PV WITHOUT STORAGE. PV is used directly when coincident with CS demand. Surplus is treated as grid export potential; deficits are grid import. Battery, chilled-water, PCM and ice storage are not part of the v1.0 product baseline. The storage investigation is preserved as a research branch.

v1.3 Advanced Grid Economics

MetricValueEvidence
Grid import6424.38 MWh/aCALCULATED FROM HOURLY MATCHING
Grid export30653.60 MWh/aCALCULATED FROM HOURLY MATCHING
Curtailed export0.00 MWh/aCALCULATED
Import cost€ 642437.52/aCALCULATED · TARIFF PROJECT INPUT
Export revenue€ 459803.98/aCALCULATED · TARIFF PROJECT INPUT
Fixed grid cost€ 0.00/aPROJECT INPUT / ASSUMED
Peak grid import4724.98 kWCALCULATED FROM 8760 HOURS
Demand charge€ 0.00/aCALCULATED · PROJECT INPUT
Weighted import price€ 100.00/MWhCALCULATED
Weighted export price€ 15.00/MWhCALCULATED
Net grid energy cost€ 182633.55/aCALCULATED
Break-even export price€ 20.96/MWhCALCULATED DIAGNOSTIC

v1.3 uses the actual 8760 hourly import/surplus arrays. Off-peak/peak tariffs, demand charge and export limit are PROJECT INPUT / ASSUMED. Economic post-processing only: no storage, no load shifting and no change to the physical baseline. Taxes and detailed grid fees are not yet modelled.

v1.4 Project Economics / Energy Cash Flow

MetricValueEvidence / boundary
Direct PV use6886.64 MWh/aCALCULATED FROM 8760 HOURS
Direct PV avoided-purchase value€ 688664.48/aCALCULATED · COINCIDENT IMPORT TARIFF
Export revenue€ 459803.98/aFROM v1.3 GRID ECONOMICS
Gross energy value€ 1148468.45/aCALCULATED
Annual project OPEX€ 0.00/aPROJECT INPUT / ASSUMED
Year-1 net project cash flow€ 1148468.45CALCULATED · ENERGY-ONLY
Project CAPEX€ 0.00PROJECT INPUT / ASSUMED
NPV€ 11275832.56CALCULATED · ENERGY-ONLY
Simple payback- yearsCALCULATED DIAGNOSTIC
Discounted payback- yearsCALCULATED DIAGNOSTIC

Energy-only project cash flow. Direct PV is valued at the coincident import tariff; export at v1.3 tariff. Demand/fixed grid charges are reported but not claimed as avoided investment benefits because a no-PV counterfactual peak/grid contract is not yet modelled. Water value, cooling-service value, taxes, financing and full ClimaStrat CAPEX allocation are excluded.

PV Surface Diagnostics

SurfaceAreaTiltAzimuthAnnual POAInstalledGenerationSpecific yield kWh/kWp·aShare
ROOF140000.00 m²0.0°180.0°1577.32 kWh/m²a28000.00 kWp37540.24 MWh/a1340.7100.0%
SOUTH_FACADE0.00 m²90.0°180.0°859.07 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%
EAST_FACADE0.00 m²90.0°90.0°788.75 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%
WEST_FACADE0.00 m²90.0°270.0°871.02 kWh/m²a0.00 kWp0.00 MWh/a0.00.0%

Azimuth: N=0°, E=90°, S=180°, W=270°. EPW GHI/DNI/DHI = SOURCE_DATA; POA and generation = MODELLED; module efficiency, PR and albedo = ASSUMED.