ClimaStrat Project App v1.4
Engineering Workspace · Generic Geocode + Multi-Performance

← Projekte   CS-2026-SA-JED-0001 REFERENCE / LOCKED

Jeddah Reference Project

Standort
Jeddah, Saudi Arabia
Quick Assessment
10000.0 m² · 4000.0 Paneele · 50000 m³/h CALCULATED

Climate / EPW

Jeddah.epw
Jeddah-Abdulaziz.Intl.AP, SAU · 8760 h
SHA-256 bb1afd72ea9a42f2…

ARE_AZ_Abu.Dhabi-Bateen.Exec.AP.412160_TMYx.2011-2025.epw
Abu.Dhabi-Bateen.Exec.AP, ARE · 8760 h
SHA-256 1631528ee2411ae6…

HUN_NGP_Szolnok.AB.128600_TMYx.2011-2025.epw
Szolnok.AB, HUN · 8760 h
SHA-256 1664a3cfe2204bf5…

ARE_DU_Dubai.Minhad.Ab.412164_TMYx.2011-2025.epw
Dubai.Minhad.Ab, ARE · 8760 h
SHA-256 95fe708d2331b0e9…

TWN_NOR_Hsinchu.AP.467560_TMYx.2011-2025.epw
Hsinchu.AP, TWN · 8760 h
SHA-256 a1dd22c483401272…

ESP_IB_Palma.de.Mallorca.AP-Son.San.Juan.AFB.083060_TMYx.2011-2025.epw
Palma.de.Mallorca.AP-Son.San.Juan.AFB, ESP · 8760 h
SHA-256 7533d562dfae5564…

NLD_NB_Eindhoven.AP.063700_TMYx.2011-2025.epw
Eindhoven.AP, NLD · 8760 h
SHA-256 5a4dd2b22593d6bb…

Neues Szenario

Operating = ASSUMED

Scenarios

IDEPWAFDTinnxStatus
JEDDAH-0471-NX16Jeddah.epw5.016.016REFERENCE · LEGACY 🔒

Simulation Results

RunScenarioClimateWater m³/aCond hCooling hTotal MWhth/aEvidenceView / Actions
RUN-20261121225027JEDDAH-0471-NX16Jeddah.epw1615.826721587542647.717MODELLED LOCKED
RUN-20261009080747JEDDAH-0471-NX16Jeddah.epw1615.826721587542647.717MODELLED LOCKED

CS-ENGINE-0.4.7.1 · forced-flow baseline · mixed convection NOT APPLIED · physical yield TO BE VALIDATED.

Energy & PV Baseline

Energy result: RUN-20261009080747 · Scenario: JEDDAH-0471-NX16

MetricValueEvidence
Cooling electricity661.93 MWh/aCALCULATED · COP ASSUMED
Fan electricity0.00 MWh/aMODELLED / CALCULATED
Fan Δp{} Pa-
Fan electric power{} WMODELLED
Gap air velocity{} m/sMODELLED
Fan Reynolds number{}MODELLED
Flow regime{}CALCULATED CLASSIFICATION
f laminar (64/Re){}CALCULATED COMPARATOR
f Swamee-Jain{}MODELLED COMPARATOR
f Churchill{}MODELLED · TRANSITION CAPABLE
Δp gap – Swamee-Jain{} PaMODELLED COMPARATOR
Δp gap – Churchill{} PaMODELLED COMPARATOR
Local loss ΣK{}ASSUMED
Δp local{} PaCALCULATED FROM ASSUMED K
Δp system{} PaMODELLED
Fan efficiency η{}ASSUMED
Fan modelMANUAL_SPECIFIC_LOADMODELLED
Pump electricity0.00 MWh/aMODELLED / CALCULATED
Pump total flow{} L/minCALCULATED
Pump peak flow{} L/minMODELLED
Coolant design ΔT{} KASSUMED
Hydraulic zones{}CALCULATED FROM PANELS / ZONE
Panels / hydraulic zone{}ASSUMED / TO BE ENGINEERED
Zone pipe{} mm · {} mASSUMED
Zone pipe velocity{} m/sMODELLED
Zone pipe Δp{} PaMODELLED
Main hydraulic loops{}ASSUMED ARCHITECTURE
Main pipe{} mm · {} mASSUMED
Main pipe velocity{} m/sMODELLED
Main pipe Δp{} PaMODELLED
Channel flow{} L/minCALCULATED
Coolant velocity{} m/sMODELLED
Coolant Reynolds{}MODELLED
Channel Δp{} PaMODELLED · RECTANGULAR LAMINAR
Pump system Δp{} PaMODELLED
Pump electric power{} WMODELLED
Pump peak electric power{} WMODELLED
Optimizer criterion{}MODELLED DESIGN SEARCH
Optimizer balanced loops{}MODELLED
Optimizer balanced main Ø{} mmMODELLED
Optimizer balanced pump energy{} MWh/aMODELLED COMPARATIVE
Optimizer balanced peak velocity{} m/sMODELLED
Optimizer feasible variants{} / {}CALCULATED
Energy-min variant{} loops · Ø {} mm · {} MWh/aMODELLED COMPARATIVE
Infrastructure-min variant{} loops · Ø {} mm · proxy {} m³MODELLED PROXY
Pareto variants0CALCULATED
Total CS electricity661.93 MWh/aCALCULATED
EPW GHI2225.62 kWh/m²aSOURCE_DATA
PV area7000.00 m²CALCULATED FROM SURFACES
Installed PV1400.00 kWpCALCULATED
PV generation2616.06 MWh/aMODELLED
PV reference planeORIENTED_POA_ISOTROPIC_SKYMODELLED
PV transpositionISOTROPIC_SKYMODELLED
Annual energy balance1954.13 MWh/aCALCULATED
Hourly CS load661.93 MWh/aCALCULATED FROM HOURLY MODEL
PV direct use335.13 MWh/aCALCULATED · NO STORAGE
PV surplus2280.93 MWh/aCALCULATED · NO STORAGE
Grid import326.80 MWh/aCALCULATED · NO STORAGE
PV self-consumption0.128CALCULATED · DIRECT PV / PV
CS self-sufficiency0.506CALCULATED · DIRECT PV / CS LOAD
Peak CS load198.39 kWMODELLED / CALCULATED
Peak PV1192.25 kWMODELLED
Peak grid import170.41 kWCALCULATED

Hourly Energy Diagnostics

DiagnosticValueEvidence
CS active hours8750CALCULATED
Hours with PV surplus4014CALCULATED
Hours with grid import4740CALCULATED
Active CS hours fully supplied by PV4010CALCULATED · NO STORAGE
Maximum PV surplus1134.08 kWCALCULATED
Maximum deficit / grid import170.41 kWCALCULATED

Monthly Energy Matching

MonthCS MWhPV MWhDirect MWhSurplus MWhGrid MWhCS self-suff.PV self-cons.
Jan27.52160.3413.25147.0914.2748.2%8.3%
Feb25.37168.5512.44156.1212.9349.0%7.4%
Mar35.42232.0019.18212.8216.2454.1%8.3%
Apr44.62249.7824.76225.0219.8655.5%9.9%
May64.78273.3334.06239.2630.7252.6%12.5%
Jun70.13259.7539.01220.7431.1255.6%15.0%
Jul75.99260.0840.88219.1935.1053.8%15.7%
Aug86.86247.7844.10203.6942.7650.8%17.8%
Sep79.64224.7237.41187.3142.2247.0%16.6%
Oct71.76210.0333.89176.1437.8747.2%16.1%
Nov48.31171.6121.54150.0726.7744.6%12.6%
Dec31.53158.0814.60143.4916.9446.3%9.2%

Energy Matching by EPW Hour

EPW hourCS MWh/a-binPV MWh/a-binDirectSurplusGrid
0126.060.000.000.0026.06
0225.750.000.000.0025.75
0325.410.000.000.0025.41
0424.890.000.000.0024.89
0524.750.000.000.0024.75
0624.550.810.810.0023.74
0724.3721.7516.035.728.34
0824.9285.3824.9060.480.02
0926.29173.3826.29147.100.00
1028.05256.5828.05228.540.00
1129.79321.8429.79292.050.00
1229.78360.7029.78330.920.00
1330.38368.9230.38338.540.00
1430.55345.8130.55315.260.00
1530.12293.2330.12263.110.00
1629.33215.9229.33186.580.00
1729.24122.8529.2393.630.02
1829.1741.7223.1518.576.01
1928.906.516.050.4622.85
2028.740.660.660.0028.08
2128.670.000.000.0028.67
2227.910.000.000.0027.91
2327.330.000.000.0027.33
2426.980.000.000.0026.98

EPW hours are end-of-hour labels (1–24). Diagnostics aggregate the same hourly arrays used by v0.9.0; no storage or load shifting is applied.

v1.0 Energy Architecture

GRID-COUPLED PV WITHOUT STORAGE. PV is used directly when coincident with CS demand. Surplus is treated as grid export potential; deficits are grid import. Battery, chilled-water, PCM and ice storage are not part of the v1.0 product baseline. The storage investigation is preserved as a research branch.

v1.3 Advanced Grid Economics

MetricValueEvidence
Grid import326.80 MWh/aCALCULATED FROM HOURLY MATCHING
Grid export2280.93 MWh/aCALCULATED FROM HOURLY MATCHING
Curtailed export0.00 MWh/aCALCULATED
Import cost€ 32679.79/aCALCULATED · TARIFF PROJECT INPUT
Export revenue€ 34213.97/aCALCULATED · TARIFF PROJECT INPUT
Fixed grid cost€ 0.00/aPROJECT INPUT / ASSUMED
Peak grid import170.41 kWCALCULATED FROM 8760 HOURS
Demand charge€ 0.00/aCALCULATED · PROJECT INPUT
Weighted import price€ 100.00/MWhCALCULATED
Weighted export price€ 15.00/MWhCALCULATED
Net grid energy cost€ -1534.19/aCALCULATED
Break-even export price€ 14.33/MWhCALCULATED DIAGNOSTIC

v1.3 uses the actual 8760 hourly import/surplus arrays. Off-peak/peak tariffs, demand charge and export limit are PROJECT INPUT / ASSUMED. Economic post-processing only: no storage, no load shifting and no change to the physical baseline. Taxes and detailed grid fees are not yet modelled.

v1.4 Project Economics / Energy Cash Flow

MetricValueEvidence / boundary
Direct PV use335.13 MWh/aCALCULATED FROM 8760 HOURS
Direct PV avoided-purchase value€ 33513.14/aCALCULATED · COINCIDENT IMPORT TARIFF
Export revenue€ 34213.97/aFROM v1.3 GRID ECONOMICS
Gross energy value€ 67727.11/aCALCULATED
Annual project OPEX€ 0.00/aPROJECT INPUT / ASSUMED
Year-1 net project cash flow€ 67727.11CALCULATED · ENERGY-ONLY
Project CAPEX€ 0.00PROJECT INPUT / ASSUMED
NPV€ 664954.78CALCULATED · ENERGY-ONLY
Simple payback- yearsCALCULATED DIAGNOSTIC
Discounted payback- yearsCALCULATED DIAGNOSTIC

Energy-only project cash flow. Direct PV is valued at the coincident import tariff; export at v1.3 tariff. Demand/fixed grid charges are reported but not claimed as avoided investment benefits because a no-PV counterfactual peak/grid contract is not yet modelled. Water value, cooling-service value, taxes, financing and full ClimaStrat CAPEX allocation are excluded.

PV Surface Diagnostics

SurfaceAreaTiltAzimuthAnnual POAInstalledGenerationSpecific yield kWh/kWp·aShare
ROOF_HORIZONTAL7000.00 m²0.0°180.0°2198.37 kWh/m²a1400.00 kWp2616.06 MWh/a1868.6100.0%

Azimuth: N=0°, E=90°, S=180°, W=270°. EPW GHI/DNI/DHI = SOURCE_DATA; POA and generation = MODELLED; module efficiency, PR and albedo = ASSUMED.